5.4.3.3

Optimising the Imax controller

Using the Lenze setting of the current limitation controller, the drive is stable:

Most applications do not require optimisation.
The setting of the current limitation controller must be adapted if

• power control including great moments of inertia is performed.

• Recommendation: Increase of the reset time Ti (

C00074/1

) of the I

max

controller.

• vibrations occur in the V/f control (VFCplus + encoder) mode during the intervention of the

current limitation controller.

• Recommendation: Increase of the reset time Ti (

C00074/1

) of the I

max

controller.

• overcurrent errors (e.g. OC3) occur due to load impulses or too high acceleration ramps.

• Recommendation: Reduction of the gain Vp (

C00073/1

) and reset time Ti (

C00074/1

) of the

I

max

controller.

Note!

V

min

boost is automatically calculated by the motor parameter identification using the

data specified on the motor nameplate so that a no-load current of approx. 0.8 I

rated

motor

results at the slip frequency of the machine.

V/f control (VFCplus + encoder)
If V/f control (VFCplus + encoder) is selected, we recommend a decidedly lower V

min

boost:

• In this case, select a V

min

boost which ensures that approx. 50 % of the rated motor

current flows at slip frequency when the motor is idling.

Parameter

Info

Lenze setting

Value Unit

C00073/1

VFC: Vp Imax controller

0.25

C00074/1

VFC: Ti Imax controller

65 ms