C00008 | original application|control source, 16 parameter reference, Terminal assignment of the control modes 10 – Lenze 8400 User Manual

Page 744

Advertising
background image

16

Parameter reference

16.2

Parameter list | C00008

744

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Terminal assignment of the control modes 10 ... 16

C00008

"Actuating drive speed" TA

Input/output

10: Terminals 0

12: Terminals 2

14: Terminals 11

16: Terminals 16

RFR

Controller enable / Reset of error message

DI1

Fixed setpoint 1/3

Change of direction of

rotation

Fixed setpoint 1/3

DI2

Fixed setpoint 2/3

Activate manual DC-

injection braking (DCB)

Fixed setpoint 2/3

DI3

Activate manual DC-injection

braking (DCB)

Quick stop

Motor potentiometer:

Increase speed

CW rotation quick stop

DI4

Change of direction of rotation

Motor potentiometer:

Decrease speed

CCW rotation quick stop

DI5

-

-

-

-

DI6

-

-

-

-

A1U

Main speed setpoint (10 V ≡ 100 % reference speed)

TA "Table positioning"

Input/output

10: Terminals 0

12: Terminals 2

14: Terminals 11

16: Terminals 16

RFR

Controller enable / Reset of error message

DI1

-

-

Positive limit switch

-

DI2

-

-

Negative limit switch

-

DI3

Positive limit switch

-

-

-

DI4

Negative limit switch

Positioning profile, array bit (valency 2)

Quick stop

DI5

Positioning profile,

array bit (valency 2)

Positioning profile, array bit (valency 1)

Positioning profile,

array bit (valency 2)

DI6

Start of profile generation

A1U

Main speed setpoint (10 V ≡ 100 % reference speed)

"Switch-off positioning" TA

Input/output

10: Terminals 0

12: Terminals 2

14: Terminals 11

16: Terminals 16

RFR

Controller enable

Controller enable / Reset of error message

DI1

Fixed setpoint 1/3

Stop function 1

Fixed setpoint 1/3

DI2

Fixed setpoint 2/3

Stop function 2

Selection: Pre-switch off 1

Fixed setpoint 2/3

DI3

Reset error message

CW rotation quick stop

Selection: Switch-off position 1

CW rotation quick stop

DI4

Change of direction of

rotation

CCW rotation quick stop

Selection: Switch-off position 2

CCW rotation quick stop

DI5

-

-

Stop function 2

-

DI6

-

-

Selection: Pre-switch off 2

-

A1U

Main speed setpoint (10 V ≡ 100 % reference speed)

Parameter | Name:

C00008 | Original application|control source

Data type: UNSIGNED_16

Index: 24567

d

= 5FF7

h

Display of the originally selected technology application and the originally selected control mode.

• This parameter shows the selection that was set with

C00005

and

C00007

before a change in the I/O level or the

application level was carried out.

• For diagnostic purposes, this display serves to determine whether there is a standard interconnection in the

controller or a change carried out by the user.

Selection list

(read only)

Info

0 Free|Free

Application: Interconnection has been changed.

I/O level: Interconnection has been changed.

10 Free|Terminal0

Application: Interconnection has been changed.

I/O level: "Terminals 0" control mode