9 servo control (sc), Servo control (sc), 5motor control (mctrl) – Lenze 8400 User Manual

Page 219

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

219

5

Motor control (MCTRL)

5.9

Servo control (SC)

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.9

Servo control (SC)

Field-oriented servo control (SC) is based on a decoupled, separate control of the torque-producing

and the field-producing current component. The motor control is based on a field-oriented,

cascaded controller structure with feedback function and enables dynamic and stable operation in

all of the four quadrants.

Generally, the servo control offers the same advantages as the sensorless vector control (SLVC), i.e.

compared to the V/f characteristic control, the servo control (SC) can be used to achieve

• A higher maximum torque throughout the entire speed range
• A higher speed accuracy
• A higher concentricity factor
• A higher level of efficiency
• The implementation of torque-actuated operation with speed limitation
• The limitation of the maximum torque in motor and generator mode for speed-actuated

operation

Stop!

• Servo control (SC) is only suitable for asynchronous motors.
• We recommend to select a power-adapted combination of inverter and motor.
• The Lenze setting permits the operation of a power-adapted motor. Optimal

operation is only possible if either:

• the motor is selected via the Lenze motor catalogue
• the motor nameplate data are entered and motor parameter identification is

carried out afterwards

- or -

• the nameplate data and equivalent circuit data of the motor (motor leakage

inductance and mutual motor inductance, slip compensation and motor stator

resistance) are entered manually.

• When you enter the motor nameplate data, take into account the phase connection

implemented for the motor (star or delta connection). Only enter the data applying to

the selected connection type.

• Speed feedback parameterisation is required.

Advertising