C00448 | digout decoupling value, C00449 | freqinxx_dnout_p, C00449/1 – Lenze 8400 User Manual

Page 830: C00448, Specifyin, 16 parameter reference

Advertising
background image

16

Parameter reference

16.2

Parameter list | C00448

830

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00448

C00449

C00455

Parameter | Name:

C00448 | DigOut decoupling value

Data type: UNSIGNED_16

Index: 24127

d

= 5E3F

h

From version 02.00.00

Definition of the value the digital output terminals are to have in the decoupled state.

• Bit set = HIGH level

Configuring exception handling of the output terminals

Setting range

(min. hex value | max. hex value)

Lenze setting

0x0000

0xFFFF 0x0000 (decimal: 0)

Value is bit-coded: (= bit set)

Bit 0  Reserved
Bit 1  DigOut1_ON
Bit 2  DigOut2_ON
Bit 3  Reserved
Bit 4  Reserved
Bit 5  BrakeRelease_ON
Bit 6  Reserved
Bit 7  Reserved
Bit 8  Reserved
Bit 9  Reserved

Bit 10  Reserved
Bit 11  Reserved
Bit 12  Reserved
Bit 13  Reserved
Bit 14  Reserved
Bit 15  Reserved

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00449 | FreqInxx_dnOut_p

Data type: INTEGER_32

Index: 24126

d

= 5E3E

h

From version 06.00.00

Output of the encoder position of the DI1/DI2 frequency input

Display range

(min. value | unit | max. value)

-2147483647

Incr.

2147483647

Subcodes

Info

C00449/1

FreqIn12_dnOut_p

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00455 | FB_call table

Data type: UNSIGNED_16

Index: 24120

d

= 5E38

h

This code is for device-internal use only and must not be written to by the user!