18.1

Function blocks | L_GainOffsetP_2

1296

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.1.90

L_GainOffsetP_2

This FB can amplify an analog input signal and then add an offset to it. Preferably to be

interconnected directly after the analog input terminals.

• The internal calculations (addition and subtraction) are carried out with 32 bits without

overflow/underflow. Division is not remainder considered.

• Gain and offset are selected via parameters.
• The value provided at the nOut_a output is internally limited to ±199.99 %.

Inputs

Outputs

Parameter

Function

Identifier

Data type

Information/possible settings

nIn_a

INT

Input signal

• Scaling: 16384 ≡ 100 %

Identifier

Data type

Value/meaning

nOut_a

INT

Output signal

• Internal limitation to ±199.99 %

Parameter

Possible settings

Info

C00677/3

-199.99

%

199.99 Gain factor

• Lenze setting: 100.00 %

• 199.99 % ≈2

C00677/4

-199.99

%

199.99 Offset

• Lenze setting: 0.00 %

/B*DLQ2IIVHW3B

Q,QBD

Q2XWBD

2IIVHW

*DLQ

&

&

“

“



nOut_a

nIn_a Gain factor

(

) Offset

+

=