5 monitoring of the rpdos for data reception, 6 configuring exception handling of the can pdos, Monitoring of the rpdos for data reception – Lenze 8400 User Manual

Page 656: Configuring exception handling of the can pdos, 11 canopen option

Advertising
background image

11

CANopen option

11.8

Process data transfer

656

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.8.5

Monitoring of the RPDOs for data reception

For RPDO1 ... RPDO4 each, a monitoring time can be parameterised within which the RPDO must

arrive. If the RPDO is not received within the monitoring time or not with the configured sync, the

response parameterised for each RPDO takes place.

Short overview: Parameters for RPDO monitoring

11.8.6

Configuring exception handling of the CAN PDOs

This function extension is available from version 02.00.00!

Exception handling for the CAN PDOs in the event of an error can be set via decoupling

configuration and decoupling values.

• Bit coded selection is carried out in

C00342/1

for the process data words read by the bus,

defining the events that will trigger decoupling.

• Bit coded selection is carried out in

C00342/2

for the process data words output by the

application, defining the events that will trigger decoupling.

Parameter

Info

Lenze setting

Value Unit

C00357/1...3

CAN1...3_IN monitoring time

3000 ms

C00593/1...3

Resp. to CAN1...3_IN monitoring

No response

Bit

Event

Bit 0  BusOff_MsgErr
Bit 1  Warning
Bit 2  NodeStopped
Bit 3  HeartBeatEvent
Bit 4  CAN1_In_Überw.
Bit 5  CAN2_In_Überw.
Bit 6  CAN3_In_Überw.
Bit 7  Reserved
Bit 8  Reserved
Bit 9  Reserved

Bit 10  Reserved
Bit 11  Reserved
Bit 12  Reserved
Bit 13  Reserved
Bit 14  Trouble
Bit 15  Fault