Parameter list | C02866

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C02866

C02867

Parameter | Name:

C02866 | MCTRL: Special settings

Data type: UNSIGNED_8

Index: 21709

d

= 54CD

h

From version 12.00.00

Selection list

0 No
1 Yes

Subcodes

Lenze setting

Info

C02866/1

1: Yes

Motor ident.: Current controller par. from C075 C076

Automatic motor data identification

C02866/2

0: No

Motor phase error monitoring before operation

Motor phase error monitoring before operation

C02866/3

0: No

Brake chopper DC-bus slave

Control of multiple internal brake choppers in the DC-

bus system

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C02867 - Identification procedure

Data type: UNSIGNED_8

Index: 21708

d

= 54CC

h

From version 12.00.00

Selection of the identification procedure for motor parameter identification

Automatic motor parameter identification

Selection list

Info

0 automatic

Automatic selection of the optimum identification

procedure:

• For synchronous motors, the extended identification

procedure is always used.

• For asynchronous motors with a rated motor power

of up to 11 kW, the basic identification procedure is

used.

• For asynchronous motors with a rated motor power

of more than 11 kW, the extended identification

procedure is used.

1 standard identification

• Only for asynchronous motors.

• Duration approx. 30 s

2 extended identification

• Stands out due to increased accuracy of the

determined motor parameters.

• Also supports synchronous motors and asynchronous

motors with a power of more than 11 kW.

• Duration approx. 80 s

Subcodes

Lenze setting

Info

C02867/1

0: automatic

Motor parameter identification: Process

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1