Parameter list | C00234

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00234

C00235

C00236

C00241

Parameter | Name:

C00234 | Oscillation damping influence

Data type: UNSIGNED_16

Index: 24341

d

= 5F15

h

Oscillation damping

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

250.00 5.00 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00235 | Oscillation damping filter time

Data type: UNSIGNED_8

Index: 24340

d

= 5F14

h

Oscillation damping

Setting range

(min. value | unit | max. value)

Lenze setting

2

ms

250 32 ms

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00236 | Field weakening oscillation damping

Data type: UNSIGNED_8

Index: 24339

d

= 5F13

h

Oscillation damping for idling machines

Oscillation damping

Setting range

(min. value | unit | max. value)

Lenze setting

0

40 14

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00241 | L_NSet_1: Hyst. NSet reached

Data type: INTEGER_16

Index: 24334

d

= 5F0E

h

The

L_NSet_1

FB: Hysteresis window for the zero detection of the speed output setpoint

• The speed threshold for the zero detection is 1 %

Setting range

(min. value | unit | max. value)

Lenze setting

0.00

%

100.00 0.50 %

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100