2 hardware limit switch, Hardware limit switch, Negativ – Lenze 8400 User Manual

Page 476: 8basic drive functions (mck), Stop

Advertising
background image

8

Basic drive functions (MCK)

8.4

Basic settings

476

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

8.4.3.2

Hardware limit switch

The travel range limits are monitored by means of limit switches via the inputs bLimitSwitchPos and

bLimitSwitchNeg of the

LS_MotionControlKernel

system block.

• The two inputs react to the TRUE state.
• In

TA "Table positioning"

, the two inputs are connected to the digital inputs provided for

connection of the limit switches.

Behaviour when hardware limit switches are active

• If one of the two monitoring inputs is set to TRUE:

• The error response "TroubleQuickStop" takes place in the Lenze setting, i.e. the drive is

brought to a standstill in the deceleration time set for the quick stop function and does so

irrespective of the setpoint selection. The error response can be parameterised in

C00595/1

and

C00595/2

.

• The error message "Ck01: Pos. HW limit switch" or. "Ck02: Neg. HW limit switch" is entered

in the logbook.

• Bit 10 ("Pos. HW-Limit Detected") or bit 11 ("Neg. HW-Limit Detected") is set in the

MCK

status word

.

• Depending on the parameterised fault response, the drive cannot traverse until the error has

been acknowledged.

Stop!

The limit switches are only evaluated if the limit switches for the respective operating

mode have been activated (see the following table)!

Operating mode

Hardware limit switch effective

Speed follower

Yes (adjustable in

C01219

- bit 2)

Homing

Depending on the selected homing mode (see description of the homing modes)

Manual jog

No (adjustable in

C01230

- bit 2)

Positioning

Yes

Stop

Yes

Position follower

Yes (adjustable in

C01218

- bit 2)

Note!

If the digital inputs used for connecting the limit switches are fail-safe inputs (tripping

at LOW level), you simply change the terminal polarity of the corresponding digital

inputs in

C00114

.

Note!

An activated limit switch can be retracted again by manual jog in the opposed direction

or with the "Retract limit switch" function.

Retracting of an operated limit switch

( 512)

Only in the "

Manual jog

" operating mode, retracting of the limit switch resets bit 10

("Pos. HW-Limit Detected") or bit 11 ("Neg. HW-Limit Detected") in the

MCK status word

.

Advertising