C00181 | time settings, C00182 | l_nset_1: s-ramp time pt1, C00184 | autofailreset repetition time – Lenze 8400 User Manual

Page 787: C00185 | autofailreset remaining time, C00186 | max. number of autofailreset processes, Or the time set in, C00181/1, The 7-s, C00182, C00184

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

787

16

Parameter reference

16.2

Parameter list | C00181

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00181

C00182

C00184

C00185

C00186

Parameter | Name:

C00181 | Time settings

Data type: UNSIGNED_16

Index: 24394

d

= 5F4A

h

From version 06.00.00

Time for device search function (optical location)

Device search function

Setting range

(min. value | unit | max. value)

0

s

6000

Subcodes

Lenze setting

Info

C00181/1

5 s

Time - device search function

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00182 | L_NSet_1: S-ramp time PT1

Data type: INTEGER_16

Index: 24393

d

= 5F49

h

FB

L_NSet_1

: PT1 S-ramp time for the main setpoint ramp function generator

• Only effective with activated ramp rounding (

C00134

= "1").

Setting range

(min. value | unit | max. value)

Lenze setting

0.01

s

50.00 20.00 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 100

Parameter | Name:

C00184 | AutoFailReset repetition time

Data type: UNSIGNED_16

Index: 24391

d

= 5F47

h

After the time set here has expired, an error message of an error that has occurred will be reset automatically if

"AutoFailReset" had been configured correspondingly in

C00188

.

AutoFailReset function

Setting range

(min. value | unit | max. value)

Lenze setting

1

s

600 3 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00185 | AutoFailReset remaining time

Data type: UNSIGNED_16

Index: 24390

d

= 5F46

h

Display of the residual runtime of the "AutoFailReset" function

AutoFailReset function

Display range

(min. value | unit | max. value)

0

s

600

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00186 | Max. number of AutoFailReset processes

Data type: UNSIGNED_8

Index: 24389

d

= 5F45

h

Maximum number of "AutoFailReset" procedures

AutoFailReset function

Setting range

(min. value | unit | max. value)

Lenze setting

1

16 4

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1