5

Motor control (MCTRL)

5.4

V/f characteristic control (VFCplus)

156

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Note!

87-Hz operation
4-pole asynchronous motors which are designed for a rated frequency of f = 50 Hz in star

connection can be operated in delta connection when being constantly excited up to f =

87 Hz.

• Advantages:

• Higher speed-setting range
• 73% higher power output in case of standard motors

• Motor current and motor power increase by the factor

.

• The field weakening range starts above 87 Hz.
• Generally, this process can also be used with motors which have different numbers of

pole pairs. In case of 2-pole asynchronous motors, the mechanical limit speed must be

maintained.