C00354

C00355

Parameter | Name:

C00354 | COBID

Data type: UNSIGNED_32

Index: 24221

d

= 5E9D

h

Setting of the default COBID according to CANopen

• A change in the COBID will not be effective until a CAN reset node is performed.

CANopen Option/CAN on board

Setting range

(min. hex value | max. hex value)

0x00000000

0xFFFFFFFF

Value is bit-coded:

Info

Bit 0 COBID Bit0

• Bit 0 ... 10: COB-ID

• Bit 11 ... 30: Reserved

• Bit 31: PDO invalid (is not transmitted)

... ...

Bit 31 PDO invalid

Subcodes

Lenze setting

Info

C00354/1

0x00000201

COBID CAN1_IN

C00354/2

0x00000181

COBID CAN1_OUT

C00354/3

0x00000301

COBID CAN2_IN

C00354/4

0x00000281

COBID CAN2_OUT

C00354/5

0x00000401

COBID CAN3_IN

C00354/6

0x00000381

COBID CAN3_OUT

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00355 | Active COBID

Data type: UNSIGNED_16

Index: 24220

d

= 5E9C

h

Display of the COBID of the PDOs that is active in the CAN stack

CANopen Option/CAN on board

Display range

(min. value | unit | max. value)

0

2047

Subcodes

Info

C00355/1

Active COBID CAN1_IN

C00355/2

Active COBID CAN1_OUT

C00355/3

Active COBID CAN2_IN

C00355/4

Active COBID CAN2_OUT

C00355/5

Active COBID CAN3_IN

C00355/6

Active COBID CAN3_OUT

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1