Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

73

3

Commissioning

3.8

Commissioning of the "Table positioning" technology application

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

4. Recommendation: Set an offset in the Homing home offset input field (

C01227/1

) to prevent

the machine from stopping at an activated limit switch.

• Background: The load machine can also leave the travel range limit switch. There follows a

return to the home position that was set with the positive edge of the travel range limit

switch.

5. Set suitable profile parameters for the homing:

6. After setting the parameters for the homing, click the Back button to change back to the

OverviewSignal flow dialog level.

Parameter

Lenze setting

Info

Value Unit

S-ramp time

(

C01226/1

)

0.000 s

S-ramp time for reference search/homing.

• Setting "0 s" ≡ no rounding

Start speed

(

C01224/1

)

720.0000 unit/s

Starting speed for approaching the pre-stop signals.

Start acceleration

(

C01225/1

)

720.0000 unit/s

2

Starting acceleration for the starting speed ramps.