6.1.1

Change function assignment

The internal processing function of the digital input terminals DI1/DI2 and DI5/DI6 can be

reconfigured in

C00115

if necessary. In this way, these input terminals can alternatively be used as

frequency or counting inputs in order to implement the following functions:

• Detection of the input frequency
• Detection and processing of two unipolar input frequencies to one bipolar frequency
• Counting of input pulses
• Evaluation of the speed feedback (HTL encoder) for the motor control (speed-controlled

operation)

You can find detailed information on the respective function assignment in the following

subchapters:

Using DI1(5) and DI2(6) as digital inputs

( 306)

Using DI1(5) and DI2(6) as frequency inputs

( 307)

Using DI1(5) as counting input

( 312)

Reconfiguring DI3(4) to output DO1(2)

( 316)

C00115/1: Function assignment DI1 and DI2

C00115/2: Function assignment of DI5 and DI6

Function assignment

DI1 / DI5

DI2 / DI6

0 DI1(5)=In / DI2(6)=In

Digital input

Digital input

1 DI1(5)=FreqIn / DI2(6)=In

Frequency input

Digital input

2 DI1(5)&DI2(6)=FreqIn (2-track)

Frequency input (2-track)

3 DI1(5) = FreqIn / DI2(6)=direction

Frequency input

(speed)

Frequency input

(direction)

4 DI1(5)=CountIn / DI2(6)=In

Count input

Digital input

Note!

• In the Lenze setting of

C00115

, the digital input terminals DI1/DI2 and DI5/DI6 have

been configured as "normal" digital inputs.

• The digital input terminals DI3 ... DI4 are basically designed as "normal" digital inputs

or as digital outputs through reconfiguration.

• Very high pulse frequencies can be measured at the DI1/DI2 and DI5/DI6 input

terminals if the latter have been configured as frequency or counting inputs in

C00115

. Scanning is then carried out within less than μs instead of the otherwise

usual scanning rate of 1 kHz (1 ms).