667

11

CANopen option

11.9

Parameter data transfer

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

11.9.3.3

Read block parameters

Task: The firmware version (code

C00099

) is to be read from the parameter set of the controller with

the node address "12". The firmware version has a length of 11 ASCII characters which are

transmitted as block parameters. Within the user data, the data width from the 2nd to the 8th byte

is assigned per block.

Telegram 1 to the drive: Read request

Response telegram 1 from the drive: Indication of the block length (11 characters)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x060C

0x40

0x9C

0x5F

0x00

0x00

0x00

0x00

0x00

Explanations on the telegram to the drive
Identifier

= 1536 + node address = 1536 + 12 = 1548 = 0x060C

(1536 = SDO1 basic identifier to the controller)

Command

= 0x40 = "Read request" (read request of a parameter from the controller)

Index

= 24575 - code number = 24575 - 99 = 24476 = 0x5F9C

Subindex

= 0 (code

C00099

does not have any subcodes)

Identifier

User data

1st byte

2nd byte 3rd byte

4th byte

5th byte

6th byte

7th byte

8th byte

Command

Index

Subindex

Data 1

Data 2

Data 3

Data 4

0x058C

0x41

0x9C

0x5F

0x00

0x0B

0x00

0x00

0x00

Explanations on the telegram from the drive
Identifier

= 1408 + node address = 1408 + 12 = 1420 = 0x058C

(1408 = SDO1 basic identifier from the controller)

Command

= 0x41 = "Read response" (response is block telegram)

Index

as in telegram to the drive

Subindex
Data 1 ... 4

= 0x0000000B = data length of 11 characters in the ASCII format