18 function library – Lenze 8400 User Manual

Page 1314

Advertising
background image

18

Function library

18.1

Function blocks | L_MPot_1

1314

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Outputs

Parameter

Identifier

Data type

Value/meaning

nOut_a

INT

Output signal

Parameter

Possible settings

Info

C00800

-199.99

%

199.99 Upper limit

• Lenze setting: 100.00 %

C00801

-199.99

%

199.99 Lower limit

• Lenze setting: -100.00 %

C00802

0.1

s

6000.0 Acceleration time

• Lenze setting: 10.0 s

C00803

0.1

s

6000.0 Deceleration time

• Lenze setting: 10.0 s

C00804

Inactive function

• Selection of response when

deactivating the motor

potentiometer via the input

bInAct.

• Lenze setting: 0

0 No further action; nOut_a retains its

value.

1 The motor potentiometer returns to

0 % within the deceleration time T

if

2 The motor potentiometer runs to

the lower limit value (

C00801

)

within the deceleration time T

if

3 The motor potentiometer output

immediately changes to 0 %

Important for the emergency stop

function

4 The motor potentiometer output

immediately changes to the lower

limit value (

C00801

)

5 The motor potentiometer runs to

the upper limit value (

C00800

)

within the acceleration time T

ir

C00805

Init function

• Selection of response when

switching on the device.

• Lenze setting: 0

0 The output value being output

during mains power-off is saved

non-volatilely in the internal

memory of the controller. It will be

reloaded during mains power-on.

1 The lower limit value (

C00801

) is

loaded during mains power-on.

2 An output value = 0 % is loaded

during mains power-on.

C00806

Use of the motor potentiometer

• When switching to 1: YES, the

value applied to nIn_a is

automatically transferred to the

motor potentiometer.

• Lenze setting: 0

0 No
1 Yes