C01081 | l_dfrfg_1: sync. direction / tp function, C01082 | ls_writeparamlist: execute mode, C01083 | ls_writeparamlist: error status – Lenze 8400 User Manual

Page 981: C01083, Displays an, C01082, 16 parameter reference

Advertising
background image

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

981

16

Parameter reference

16.2

Parameter list | C01081

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C01081

C01082

C01083

Parameter | Name:

C01081 | L_DFRFG_1: Sync. direction / TP function

Data type: UNSIGNED_8

Index: 23494

d

= 5BC6

h

From version 12.00.00

Selection list

1 cw/ccw - without TP
2 cw - without TP
3 ccw - without TP
4 cw/ccw - with TP
5 cw - with TP
6 ccw - with TP

Subcodes

Lenze setting

Info

C01081/1

1: cw/ccw - without TP

L_DFRFG_1

: Sync. direction / TP function

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01082 | LS_WriteParamList: Execute Mode

Data type: UNSIGNED_8

Index: 23493

d

= 5BC5

h

Parameter change-over

: Selection of the activation method

Selection list

(Lenze setting printed in bold)

Info

0 by Execute

The writing of the parameter list is activated by a

FALSE/TRUE edge at the bExecute input.

1 by Input Select

The writing of the parameter list is carried out if a change

is made at the select inputs and if the controller is

initialised.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C01083 | LS_WriteParamList: Error status

Data type: UNSIGNED_16

Index: 23492

d

= 5BC4

h

Parameter change-over

: Error status:

• 0 = no error

• 33803 | 0x840B = invalid data type (e.g. STRING)

• 33804 | 0x840C = limit violation

• 33806 | 0x840E = invalid code

• 33813 | 0x8415 = no element of the selection list

• 33815 | 0x8417 = writing of the parameter not permitted

• 33816 | 0x8418 = writing of the parameter only permitted if controller is inhibited

• 33829 | 0x8425 = invalid subcode

• 33865 | 0x8449 = no parameter with subcodes

Display range

(min. value | unit | max. value)

0

34000

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1