Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

243

5

Motor control (MCTRL)

5.10

Parameterisable additional functions

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Settable switching frequencies

Tip!
The Lenze setting

C00018

= 2 (8 kHz var./drive-opt.) is the optimal value for standard

applications.

Lowering the switching frequency due to high heatsink temperatures
Exceeding the maximally permissible heatsink temperature would lead to an inhibited drive due to

the "Overtemperature" error and a torquelessly coasting motor. Therefore, if the Lenze setting is

selected, the switching frequency is reduced to the next frequency below when the heatsink

temperature has risen to 5 °C below the maximally permissible temperature. After the heatsink has

cooled down, the controller automatically switches to the next frequency above until the set

switching frequency is reached.
Switching frequency reduction due to high heatsink temperature can be deactivated via

C00144

. If

the switching frequency reduction is deactivated, the "OH1: Heatsink overtemperature" error

message will be issued when the maximally permissible heatsink temperature is reached. An "Error"

response is the result and the motor is coasting.

Selection in

C00018

1 4 kHz var./drive-optimised

21 8 kHz var./drive-opt./4 kHz min

2 8 kHz var./drive-optimised

22 16 kHz var./drive-opt./4 kHz min

3 16 kHz var./drive-optimised

23 16 kHz var./drive-opt./8 kHz min

5 2 kHz constant/drive-optimised

31 8 kHz var./min. Pv/4 kHz min

6 4 kHz constant/drive-optimised

32 16 kHz var./min. Pv/4 kHz min

7 8 kHz constant/drive-optimised

33 16 kHz var./min. Pv/8 kHz min

8 16 kHz constant/drive-optimised

Abbreviations used:

• "var.": Adaptation of the switching frequency

depending on the current

• "drive-opt.": drive-optimised modulation ("sine/delta

modulation")

• "fixed": fixed switching frequencies

• "min. Pv": additional reduction of power loss

11 4 kHz var./min. Pv
12 8 kHz var./min. Pv
13 16 kHz var./min. Pv
15 2 kHz constant/min. Pv
16 4 kHz constant/min. Pv
17 8 kHz constant/min. Pv
18 16 kHz constant/min. Pv

Parameter

Info

Lenze setting

C00144

Switching frequency reduction (temp.)

1: On