Message, Lu: undervoltage in the dc bus, Ou:dc-bus overvoltage – Lenze 8400 User Manual

Page 592: Lu: dc bus undervoltage, Xx.0123.00015, Xx.0123.00016, Xx.0123.00014, 9diagnostics & error management

Advertising
background image

9

Diagnostics & error management

9.10

Error messages of the operating system

592

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

oU: DC bus overvoltage [xx.0123.00014]

LU: DC bus undervoltage [xx.0123.00015]

oC1: Power section - short circuit [xx.0123.00016]

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has detected an overvoltage in the DC bus. To

protect the device hardware, the inverter control is

switched off.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the

controller inhibit has been switched.

• If this error message remains active longer than the

time set in

C00601

, a "Fault" is tripped.

• Reduce load in generator mode.

• Use a brake resistor.

• Use a regenerative power supply unit.

• Establish a DC-bus connection.

Response (Lenze setting printed in bold)

Setting:

C00600/1

( Adjustable response)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has detected a DC bus undervoltage. The

inverter control is switched off because the drive

properties of the motor control cannot be provided

anymore due to the DC bus undervoltage.

• Depending on the configuration of the auto-start lock

function, set

C00142

so that, when this error is

tripped, the controller only restarts after the

controller inhibit has been switched.

• Switch on mains supply or ensure sufficient supply via

DC bus.

• Adjust setting in

C00142

if required.

Response (Lenze setting printed in bold)

0: No Reaction  1: Fault  2: Trouble  3: TroubleQuickStop  4: WarningLocked  5: Warning  6: Information

Cause

Remedy

The device has recognised a short circuit of the motor

phases. To protect the device electronics, the inverter

control is switched off.

• Mostly, incorrectly executed motor connections are

the cause.

• If the device is inappropriately dimensioned with

regard to the motor load and the current limitation in

the controller (Imax controller) is set incorrectly, this

error message may also occur.

Motor control: Defining current limits

• Check motor connections and the corresponding plug

connector on the device.

• Only use permissible combinations of device power

and motor power.

• Do not set the dynamics of the current limitation

controller too high.