5

Motor control (MCTRL)

5.10

Parameterisable additional functions

246

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Short overview of the relevant parameters:

How to parameterise the flying restart function:

1. Activate the flying restart circuit by selecting "1: On" in

C00990

.

• Every time the controller is enabled, a synchronisation to the rotating or standing drive

is carried out.

When the Lenze setting is used, most applications do not require additional controller

settings.
If additional settings are necessary, proceed as follows:

2. Define the process and hence the speed range/rotational frequency range in

C00991

which

is to be examined by the flying restart circuit:

• positive speed range (n

0 rpm)

• negative speed range (n

0 rpm)

• total speed range

3. Define the starting frequency.

The starting frequency which defines the starting point of the flying restart function is 10

or -10 Hz for processes 0 ... 3 and has been pre-optimised for standard motors.
If process 4 is selected in

C00991

, an arbitrary starting frequency can be defined via

C00992

. This is especially recommended for motors with higher rated frequencies.

• We recommend to define a starting frequency of approximately 20 % of the rated motor

frequency to enable a safe and fast connection to standing drive systems.

• For systems with a known search speed (e.g. torque-controlled drive systems which are

to synchronise to a defined speed) the starting value can be adapted to reduce the flying

restart time.

4. Set the flying restart current in

C00994

.

We recommend setting a flying restart current of 10 % ... 25 % of the rated motor current.

• During a flying restart process, a current is injected into the motor to identify the speed.
• Reducing the current causes a reduction of the motor torque during the flying restart

process. A short-time starting action or reversing of the motor is prevented with low

flying restart currents.

• An increase of the current improves the robustness of the flying restart function.

Parameter

Info

Lenze setting

Value Unit

C00990

Flying restart fct.: Activate

Off

C00991

Flying restart fct.: Process

-n...+n | Start: +10 Hz

C00992

Flying restart fct.: Start frequency

5 Hz

C00993

Flying restart fct: Int. time

300 ms

C00994

Flying restart fct.: Current

25.00 %