Basic drive functions (MCK)

8.4

Basic settings

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Re-activation after acknowledging the error
When the error has been acknowledged and the limit switch is still active, the following action is

required for a renewed activation of the monitoring depending on the operating mode:

Operating mode

Action for (re) activation

Speed follower

Limit switch is activated and setpoint in direction of the activated limit switch is pending

Note: If the setpoint e.g. is specified via an analog potentiometer, potentiometer noise can

mean an unintentional setpoint causing the error to be set again.

Homing

Limit switch is activated and bHomStartStop = TRUE

Manual jog

Limit switch is activated and manual jog in direction of the activated limit switch

Positioning

Limit switch is activated and setpoint command has been transmitted

Stop

Setting of the operating mode

Position follower

Limit switch is activated and setpoint in direction of the activated limit switch is pending