Example
Task: Starting from the preset technology application "Actuating drive speed" and the "Terminals 0"

control mode, the DI2 digital input is to be used for choosing an alternative

acceleration/deceleration time for the main setpoint instead of for choosing the fixed setpoint 2/3.

To do this, the DI2 digital input is not to be linked to the bJogSpeed2 input but to the bJogRamp1

input of the application module.
Procedure:

1. Use the keypad to go to the menu level Applications Actuating drive speed (conf.). This menu

level contains all the configuration parameters of the "Actuating drive speed" technology

application".

Configuration parameters

( 372)

2. Navigate to the configuration parameter LA_NCtrl: bJogSpeed2 (

C00701/10

) which represents

the logical signal link of the application input bJogSpeed2.

3. Change the setting of

C00701/10

:

Change selection "16001: DigIn_bIn2" in selection "0: Not interconnected".

4. Navigate to the configuration parameter LA_NCtrl: bJogRamp1 (

C00701/13

) which represents

the logical signal link of the application input bJogRamp1.

5. Change the setting of

C00701/13

:

Change selection "0: Not interconnected" in selection "16001: DigIn_bIn2".

Tip!
The example shows that, for each input of the application block, the associated

configuration parameter (

C00700/x

or

C00701/x

) is only allowed to contain one source

that you enter.