301

5

Motor control (MCTRL)

5.16

Internal status signals | System block "LS_DeviceMonitor"

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

bMctrlI2xtOverload

BOOL

Status of the

Motor load monitoring (I2xt)

TRUE Thermal motor overload (I

2

xt) ≥ motor overload setting (

C00120

)

• Lenze setting:

C00120

= 100 %.

nMctrlI2xtRate_a

INT

Current thermal motor load (I2xt)

• Scaling: 16384 ≡ 100 %

bMctrlMotorPTC

BOOL

Status of the

Motor temperature monitoring (PTC)

TRUE Temperature monitoring: An error has been detected

bMctrlMotorTemp

BOOL

TRUE Thermal motor overload

bMctrlHeatSinkTemp

BOOL

TRUE Thermal inverter overload

• The heatsink temperature (display in

C00061

) has reached the

maximally permissible temperature. The "

oH1: Overtemperature

heatsink

" error message is pending and the "Fault" response is

activated.

• Furthermore, this output is set if the heatsink temperature has

exceeded the maximally permissible temperature for the

switching frequency set. A response with an "

oH4: Heatsink

temp.. > switch-off temp. -5°C

" error message can be set in

C00582

. In the Lenze setting, no response will be effected.

bMctrlMainsFault

BOOL

Status of the

Mains phase failure monitoring

TRUE Mains phase failure/Mains failure

bMctrlFanFault

BOOL

TRUE Fan monitoring: An error has been detected

bMctrlNmaxForFChop

BOOL

TRUE The maximum field frequency for the respective switching

frequency has been exceeded.

bMctrlShortCircuit

BOOL

TRUE Motor short circuit has been detected

bMctrlEarthFault

BOOL

TRUE Earth fault has been detected

bMctrlUVDetected

BOOL

TRUE An undervoltage has been detected

bMctrlOVDetected

BOOL

TRUE An overvoltage has been detected

bMctrlBrakeChopperFault

BOOL

Status of the

Brake resistor monitoring (I2xt)

• This output is set independent of the set error response of the monitoring

function.

TRUE The I

2

xt utilisation has reached the switch-off threshold set in

C00572

.

• Lenze setting:

C00572

= 100 %.

Identifier

DIS code | data type

Value/meaning