6.1.1.3

Using DI1(5) as counting input

General information on use as a counting input
The counting input is used for counting fast edges. A 32-bit counter counts from a parameterisable

starting value up to a parameterisable comparison value and then outputs a corresponding status

signal.

• Possible counting range: 0 ... 2

31

- 1 (0 ... 2147483647)

Function assignment 4: DI1(5)=CountIn / DI2(6)=In
This setting in

C00115

configures the input terminal DI1 or DI5 as counting input. The input

terminal DI2 or DI6 remains configured as "normal" digital input..

Note!

• The starting value must be have been set so that it is smaller than the comparison

value. Otherwise, the counter will be kept at the starting value because the condition

"Count value

Comparison value" has been satisfied.

• Note the maximum input frequency of the respective input terminal:

• DI1: f

max

= 100 kHz

• DI5: f

max

= 10 kHz