Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

773

16

Parameter reference

16.2

Parameter list | C00148

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00148

Parameter | Name:

C00148 | LS_DriveInterface: Error message config.

Data type: UNSIGNED_16

Index: 24427

d

= 5F6B

h

From version 02.00.00

Selection of the device statuses for which the bCollectedFail group error output of SB

LS_DriveInterface

is to be set

to TRUE.
Setting range

(min. hex value | max. hex value)

Lenze setting

0x0000

0xFFFF 0x0030 (decimal: 48)

Value is bit-coded: (= bit set)

Info

Bit 0  SafeTorqueOff
Bit 1  ReadyToSwitchOn
Bit 2  SwitchedOn
Bit 3  TroubleQSP

From version 06.00.00

Bit 4  Trouble
Bit 5  Fault
Bit 6  Warning
Bit 7  ImpIsActive
Bit 8  CInhIsActive
Bit 9  Fail CAN_Management

Bit 10  Reserved
Bit 11  Reserved
Bit 12  Reserved
Bit 13  Reserved
Bit 14  Lock bFail at TroubleQSP

From version 12.00.00

If this bit is set, the bFail output of the

SB

LS_DriveInterface

is also set in the "TroubleQSP"

status.

• Advantage: Even in the "TroubleQSP" status, an error

occurred before can still be recognised.

Bit 15  Use 16BitFailNo.

From version 06.00.00

If this bit is set, the short 16-bit error number

(wStateDetermFailNoShort) is also provided at the

wStateDetermFailNoLow output of the

SB

LS_DriveInterface

.

• In this case, the wStateDetermFailNoHigh output is

"0".

• Advantage: The bus transfer of the error numbers is

possible via a data word without changing the

interconnection of the technology application.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT