I/O terminals

6.5

User-defined terminal assignment

344

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Possibility 2: Change terminal assignment by means of the signal flow shown
Procedure:

1. Go to the Application parameters tab.
2. Go to the Application Parameters tab and click on the Signal flow button in order to change to

the dialog level OverviewSignal flow.

3. On the dialog level OverviewSignal flow, click on the Digital control signals button in order to

open the Digital control signals dialog box:

4. In the bJogSpeed2 list field, set the selection "0: Not interconnected".
5. In the bJogRamp1 list field, set the selection "16001: DigIn_bIn2".
6. Click on the Back button in order to close the dialog box again.