Parameter reference

16.2

Parameter list | C00600

856

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00600

C00601

C00602

C00606

Parameter | Name:

C00600 | Resp. to DC bus voltage

Data type: UNSIGNED_8

Index: 23975

d

= 5DA7

h

Configuration of monitoring of the motor control (group 3)
Selection list

1 Fault
2 Trouble

Subcodes

Lenze setting

Info

C00600/1

2: Trouble

Response to DC bus undervoltage

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00601 | Del. resp. to fault: DC bus overvoltage

Data type: UNSIGNED_16

Index: 23974

d

= 5DA6

h

Error response delay times
Setting range

(min. value | unit | max. value)

0.000

s

65.000

Subcodes

Lenze setting

Info

C00601/1

2.000 s

Delay time for triggering the "DC-bus overvoltage" error

• If a DC-bus overvoltage occurs, an error will not be

triggered until the set delay time has elapsed.

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00602 | Resp. to earth fault

Data type: UNSIGNED_8

Index: 23973

d

= 5DA5

h

Response to earth fault in the motor phase(s)
Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1

Parameter | Name:

C00606 | Resp. to motor overload (I²xt)

Data type: UNSIGNED_8

Index: 23969

d

= 5DA1

h

Response when the motor load displayed in

C00066

reaches the value "100.00 %".

Motor overload monitoring (I2xt)

Selection list

(Lenze setting printed in bold)

0 No Reaction
1 Fault
5 Warning

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1