18.1

Function blocks | L_NLim_2

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

18.1.109

L_NLim_2

This FB can mask out up to three parameterisable blocking zones within a continuous signal

characteristic.

Inputs

Outputs

Note!

A value of "0" cannot be masked out if the nIn_a input signal changes signs.

Identifier

Data type

Information/possible settings

bEnable

BOOL

Activate zone masking

FALSE The FB has been deactivated.

• The input signal is output one-to-one at the nOut_a output.

TRUE The FB has been activated.

• Zone masking of the input signal is carried out according to the

parameterised blocking zones.

nIn_a

INT

Input signal

Identifier/data type

Value/meaning

wState

WORD

Bit-coded status word

• Bits that are not listed are reserved for future extensions.

Bit 0 No blocking zone active
Bit 1 Blocking zone 1 active
Bit 2 Blocking zone 2 active
Bit 3 Blocking zone 3 active

nOut_a

INT

Output signal

• If the FB has been activated, the output signal is outside the blocking zones.

bLimitActive

BOOL

"Limitation active" status signal

TRUE The input signal is inside a blocking zones and is limited to the

respective boundary value of the blocking zone.