C00104 | quick stop setting, C00105 | decel. time - quick stop, C00106 | auto dcb: hold time – Lenze 8400 User Manual

Page 764: C00105, Time parameterised in, C00104/1, C00106, 16 parameter reference

Advertising
background image

16

Parameter reference

16.2

Parameter list | C00104

764

Lenze · 8400 protec HighLine · Reference manual · DMS 3.0 EN · 03/2013 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

C00104

C00105

C00106

Parameter | Name:

C00104 | Quick stop setting

Data type: UNSIGNED_16

Index: 24471

d

= 5F97

h

From version 12.00.00

Setting range

(min. hex value | max. hex value)

0x0000

0xFFFF

Value is bit-coded:

Bit 0 Standstill position-controlled
Bit 1 Ramp position-controlled
Bit 2 Reserved
Bit 3 Reserved
Bit 4 Reserved
Bit 5 Reserved
Bit 6 Reserved
Bit 7 Reserved
Bit 8 Reserved
Bit 9 Reserved

Bit 10 Reserved
Bit 11 Reserved
Bit 12 Reserved
Bit 13 Reserved
Bit 14 Reserved
Bit 15 Reserved

Subcodes

Lenze setting

Info

C00104/1

0x0000

Quick stop setting

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Parameter | Name:

C00105 | Decel. time - quick stop

Data type: UNSIGNED_32

Index: 24470

d

= 5F96

h

The set deceleration time determines the ramp slope at quick stop
Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.900 2.000 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000

Parameter | Name:

C00106 | Auto DCB: Hold time

Data type: UNSIGNED_32

Index: 24469

d

= 5F95

h

Hold time of the automatic DC injection brake

• The DC injection brake is applied for the time set here if the value falls below the speed setpoint set in

C00019

.

DC-injection braking

Setting range

(min. value | unit | max. value)

Lenze setting

0.000

s

999.000 0.500 s

Read access  Write access  CINH  PLC STOP  No transfer  COM  MOT

Scaling factor: 1000