5 feedrate suppression point – Rockwell Automation 8520-ARM2 9/Series CNC AMP Reference Manual Documentation Set User Manual
Page 178

Servo Parameters
Chapter 7
7-32
Function
When the following error exceeds the value entered here, the control
automatically reduces the axis feedrate by 50%. Axis feedrates remain
reduced by 50% until the following error drops below the value entered
here. At that time, the control increases the feedrate to the originally
programmed speed.
Important: The value entered here must be less than or equal to the value
entered for Excess Error, or a Warning: ”SERVO AMP FE LIMITS
CORRECTED”occurs.
Axis
Parameter
Number
Axis
Parameter
Number
(1)
[1740]
(9)
[9740]
(2)
[2740]
(10)
[10740]
(3)
[3740]
(11)
[11740]
(4)
[4740]
(12)
[12740]
(5)
[5740]
(13)
[13740]
(6)
[6740]
(14)
[14740]
(7)
[7740]
(15)
[15740]
(8)
[8740]
Range
0 to 214.10000 mm
or
0 to 8.42913 in.
Notes
Typically the value entered here is at least 10% less than the value entered
for Excess Error. If desired, the Feedrate Suppression Point can be
disabled by entering a value equal to the value entered for the Excess
Error.
This parameter must be set independently for each axis.
7.2.5
Feedrate Suppression Point