Remote I/O Parameters

Chapter 33

33-3

Function

This parameter specifies the logical rack size of the remote I/O rack as it

appears to the scanner. This is not the same as the physical rack of the

control. The scanner sees a full rack to be 128 I/O points (eight 16-bit

words). 128 I/O points is the maximum number of discrete points you can

assign to a 9/Series control through remote I/O.

Axis

Parameter Number

Mill/Lathe

Grinder

All

[142]

[147]

Range

Selection

Result

I/O points

(a)

1/4 rack

32 inputs/32 outputs

(b)

1/2 rack

64 inputs/64 outputs

(c)

3/4 rack

96 inputs/96 outputs

(d)

full rack

128 inputs/128 outputs

Notes

Every quarter rack equates to two input and two output words in PAL.

$RMI1
$RMI2
$RMI3
$RMI4
$RMI5
$RMI6
$RMI7
$RMI8

$RM01
$RM02
$RM03
$RM04
$RM05
$RM06
$RM07
$RM08

SQ0 Quarter

SQ1 Quarter

SQ2 Quarter

SQ3 Quarter

Half

Half

3/4

3/4

Full Rack

Half

The actual words used is dependant on your setting of the parameter

“Adapter Start Module Group”. With the “Adapter Start Module Group”

parameter you select the starting address for your 1/4, 1/2, 3/4 or full I/O

rack. 1/4 racks can start at any of the four quarters. 1/2 racks must start at

either the SQ0, SQ1, or SQ2 quarters. 3/4 racks must start at either SQ0 or

SQ1 quarters. Full racks must always start at the SQ0 quarter.

The PLC system installer may be able to help you determine this value.