3 velocity loop parameters – Rockwell Automation 8520-ARM2 9/Series CNC AMP Reference Manual Documentation Set User Manual

Page 206

Advertising
background image

Servo Parameters

Chapter 7

7-60

Axis

Number

Axis

Number

(1)

[1024]

(7)

[7024]

(2)

[2024]

(8)

[8024]

(3)

[3024]

(9)

[9024]

(4)

[4024]

(10)

[10024]

(5)

[5024]

(11)

[11024]

(6)

[6024]

(12)

[12024]

Range

--10.0000 to +10.0000 volts dc

Notes

This parameter must be set independently for each servo.

Important: This parameter should have a value that is less than that of the

parameter Analog Servo Pos. Voltage.

An example of this parameter would be if a 15 amp drive is combined with

a servo motor rated at 9 amps peak current, the servo card should probably

never exceed --6 volts to get the drive to output 9 amps to the motor. You

would set this parameter to --6 volts. The following equation is not valid

for servo systems that use the CNC to close the velocity loop.

--10 V (maximum servo card output) x 9 A (maximum rated motor current)

15 A (Drive output at 10V)

= --6 V (Analog Servo Positive Voltage)

The servo parameters in the sections that follow are available to configure
the velocity loop. The velocity loop is only configured for digital systems,

and analog systems that use a “Position/Velocity loop type”. These

parameters become available when the servo loop type is configured as

either “digital” or “position/velocity”.

Important: Digital systems must use the motor--mounted feedback device

(that comes pre-installed on the 8520 and 1326 digital motors) for velocity

feedback. This motor--mounted feedback must not be removed from the

motor or uncoupled from the motor shaft. Precisely oriented

motor--mounted feedback is necessary for accurate motor commutation on

digital systems.

7.3

Velocity Loop Parameters