Chapter 40

40-4

To add to the current reversal error compensation data:

cursor to the value you want to change

press the

{ADD TO VALUE}

softkey

key-in the new data

press the

[TRANSMIT]

key

Important: If a parameter value that is out of range is entered, the error

message “PARAM VALUE OUT OF RANGE” is displayed on row 0

(zero) of the CRT. If an invalid value, such as a float value (decimal

number), is entered where an integer is expected, the error message

“INVALID INPUT VALUE” is displayed in row 0 (zero).

4.

Press the

{UPDATE & EXIT}

softkey to save the modified reversal

error compensation data. The control then returns to softkey level 4.

Press the

[QUIT]

softkey to return to softkey level 4 without saving

any changes.

(softkey level 4)

REVERS

ERROR

HOME

CALIB

AXIS

CALIB

SERVO

PARAM

SPNDL

PARAM

The online home calibration parameters are used to tune the home
calibration value of each axis. Home calibration specifies the distance

from the encoder marker to the desired home position. The control moves

the home calibration distance plus the distance to the encoder marker after

the home limit switch changes from “ON” to “OFF”. Refer to chapter 5

for additional information on home calibration.

Use this procedure to access the online home calibration parameters.

1.

Place the control in E-Stop.

2.

Press the

{AXIS PARAM}

softkey.

(softkey level 3)

AXIS

PARAM

PATCH

AMP

UPDATE

BACKUP

UPLD/

DWNLD

BACKUP

AMP

40.3

Home Calibration

Parameters