Feedrate Parameters

Chapter 9

9-11

Function

Use this parameter to determine whether the Skip cycles, which are

executed when a G31 - G31.4 or G37 - G37.4 is programmed, use the

current programmed feedrate or the feedrate entered as an AMP parameter.

NO -- entered as a value for this parameter causes the control to use the

current programmed feedrate. The feedrate entered as an AMP parameter

is ignored.

YES -- entered as a value for this parameter causes the control to use the

AMP feedrate for the Skip cycle. The programmed feedrate is ignored

during skip cycle execution.

Axis

Parameter Number

Single Process

Process 1

Process 2

All

[4]

[20004]

[21004]

Range

Selection

Result

(a)

Yes

(b)

No

Notes

This parameter is a global parameter. The value applies to all axes.

For Dual Processing controls, this is a per process parameter. The value set

in the parameters applies to all of the axes assigned to that process.

9.4.1

Use AMP Skip Feedrate