Remote I/O Parameters

Chapter 33

33-6

Function

This parameter is used to enable the 9/Series remote I/O connection to

perform block transfers thru PAL. Selecting “Enable” allows block

transfer, single transfers, and pass through to occur. Selecting “Disabled”

allows only single data transfers to occur.

When downloading AMP, PAL or performing other 9/Series

communications to ODS or Mini-DNC through data highway and you are

using remote I/O to pass data to PAL ($RMON is set), this flag must be

enabled. Block transfer is the communication method used by the PLC to

pass data through, get data from, the 9/Series. If you are not using PAL to

perform remote I/O communications (PAL flag $RMON is not set) the

module will automatically be enabled for pass through communications.

When block transfers are enabled, the first input and the first output words

used for single transfers are reserved for block transfer status. The first

word in a rack is configured with the parameter “Adapter Start Module

Group”. See page 33-3 for details. For any rack starting address

configured as SQ0 this is words $RMI1 and $RMO1.

Axis

Parameter Number

Mill/Lathe

Grinder

All

[145]

[144]

Range

Selection

Result

(a)

Enabled

(b)

Disabled

Notes

Important: A softkey is available to temporarily enable block transfers.

This softkey will override the disabled setting made with this AMP

parameter until the next time power to the control is cycled or the softkey

is pressed again to disable block transfers. The softkey is intended to allow

the temporary use of DH+ pass through on systems using pass through to

communicate with ODS. If AMP is lost or on new systems that have not

had AMP downloaded, use this softkey to enable block transfers so a new

AMP (with this flag enabled) can be downloaded using remote I/O pass

through. The softkey is only available when this AMP parameter is set to

Disabled and PAL has enabled remote I/O with $RMON.

The PLC system installer may be able to help you determine this value.
END OF CHAPTER

33.6

Adapter Block Transfer