Tuning a Digital or Tachless Analog System

Appendix A

A-3

AMP Parameter

Page

For Tuning

Procedure:

Description

VE Integrator Discharge Rate

This parameter is used when a large

variation in load may occur on a moving

axis. It reduces velocity overshoot and

flattens the servo response curve.

Set to 1 (one)

7-75

Torque Offset Percentage

Use this parameter when there is a

continuous static load in one direction.

This parameter tells the control the

percentage of the servo’s maximum

torque which must be applied to

compensate for this load.

Set to 0 (zero)

7-80

Torque Offset Direction

Use this parameter when there is a

continuous static load in one direction.

This parameter tells the control the

direction to apply the torque offset

percentage.

Set to Plus

7-81

Max % rated torque (--)

Indicates the maximum torque limit for

the servo in the negative direction.

Set to final value

7-78

Max % rated torque (+)

Indicates the maximum torque limit for

the servo in the positive direction.

Set to final value

7-79

Analog Servo Pos. Voltage

Indicate the servo motor’s maximum

rated current in the positive direction

relative to amplifier output (what voltage

the servo card should signal the

amplifier to reach maximum motor rated

current).

Set to final value

7-58

Analog Servo Neg. Voltage

Indicate the servo motor’s maximum

rated current in the negative direction

relative to amplifier output (what voltage

the servo card should signal the

amplifier to reach maximum motor rated

current).

Set to final value

7-59

Peak Current as a % of RMS

Indicate the percent of the servo motors

nominal rated current (continuous duty)

the Analog Servo Pos. Voltage or

Analog Servo Neg. Voltage generate

(which ever is higher).

Set to final value

7-77