Probing Parameters

Chapter 31

31-3

Function

This parameter is used to determine when the control recognizes a signal

from a probe to execute one of the skip or probing functions. The control

recognizes a probe trigger when the probe signal is turned on or off.

Low to High -- When this parameter is set at “Low to High,” the control

recognizes a probe signal when the probe turns on (rising edge of

the signal).

Figure 31.1

Low to High Probe Transition

+5 Vdc

0 Vdc

Position data captured

at first rising edge

of the probe signal

Subsequent rising edges

(due to noise or switch

bounce) have no effect

High to Low -- When this parameter is set at “High to Low,” the control

recognizes a probe signal when the probe turns off (falling edge of

the signal).

Figure 31.2

High to Low Probe Transition

Position data captured

at first falling edge

of the probe signal

Subsequent falling edges

(due to noise or switch

bounce) have no effect

+5 Vdc

0 Vdc

Axis

Parameter

Number

All

[602]

Range

Selection

Result

(a)

Low to High

(b)

High to Low

31.3

Probe Transition