Remote I/O Parameters

Chapter 33

33-4

Function

This parameter specifies the starting quarter of the remote I/O rack.

Axis

Parameter Number

Mill/Lathe

Grinder

All

[143]

[148]

Range

(a) SQ0

(b) SQ1

(c) SQ2

(d) SQ3

Selection

Result

(a)

SQ0

(b)

SQ1

(c)

SQ0

(d)

SQ3

Notes

If the rack size is 1/4, you can start at any quarter address. If the rack size

is 1/2, SQ0, SQ1, or SQ2 must be used as the starting address. If the rack

size is 3/4, SQ0 or SQ1 must be used as the starting address. If the rack is

full, you must start at SQ0. The following table illustrates this parameters

impact to PAL:

Setting of

“Adapter Start

Module Group”

First PAL Input Word*

First PAL Output Word*

SQ0

$RMI1

$RMO1

SQ1

$RMI3

$RMO3

SQ2

$RMI5

$RMO5

SQ3

$RMI7

$RMO7

* Note the first input and output word is reserved for block transfer status when the

parameter “Adapter Block Transfer” is enabled.

The PLC system installer may be able to help you determine this value.

33.4

Adapter Start Module Group