Using AMP Applications and ODS Utilities

Chapter 2

2-21

At the workstation:

1.

Return to the main menu line of ODS.

2.

Press

[F3]

to pull down the Applications menu.

3.

Select the Download application.

4.

Press

[F4]

to pull down the Utilities menu.

5.

Select the Send AMP params utility.

6.

Select the Storage Device option.

7.

Select the file to download.

The workstation displays the message:

Waiting for response from the 1770-SB

The workstation starts downloading the selected file to the storage

device. The percentage of the file that has been transferred is

continuously updated and displayed on the screen.

When the download process is complete, the workstation displays the

message:

DOWNLOAD COMPLETE

The storage device now holds an AMP file. To download this file to the

control, use this procedure:

At the storage device:

1.

Connect the storage device to the control. Refer to your integration

and maintenance manual for more information on connecting cables.

2.

Set the baud rate switch to “1200.”

3.

Set the track select switch to “Continuous.”