4 control reset on e-stop reset – Rockwell Automation 8520-ARM2 9/Series CNC AMP Reference Manual Documentation Set User Manual

Page 644

Advertising
background image

Miscellaneous Parameters

Chapter 37

37-4

Function

This parameter forces the control to perform a control reset when the

control is brought out of E-Stop by performing an E-Stop Reset operation.

Typically E-Stop reset is performed by pressing the <E-STOP RESET>

key on the MTB panel.

A control reset performs these functions:

all modal G- and M-codes are reset to the default condition (see the
PTO parameters)

all nonmodal G- and M-codes are reset to their normal condition at
power-up

all coordinate system offsets and rotations return to their normal
condition at power-up

any MDI command is discarded

any active program is reset to the first block of the program

any user’s password that is active is deactivated, and it is necessary to
re-enter the password

TRUE -- Setting this parameter as true causes the control to execute a

control reset when E-Stop is reset with the E-Stop reset feature.

FALSE -- Setting this parameter as false will not cause the control to

execute a control reset when E-Stop is reset with the E-Stop reset feature.

A control reset may still be performed in the normal method.

Axis

Parameter

Number

All

[68]

Range

Selection

Result

(a)

True

(b)

False

Notes

This is a global parameter; the value set here applies to all axes and

processes.

37.4

Control Reset on E-Stop

Reset

Advertising