Tuning AMP at the Machine

Chapter 40

40-7

Accessing Axis Calibration Parameters

Use this procedure to access the axis calibration parameters:

1.

Press the

{AXIS PARAM}

softkey.

(softkey level 3)

AXIS

PARAM

PATCH

AMP

UPDATE

BACKUP

UPLD/

DWNLD

BACKUP

AMP

2.

Press the

{AXIS CALIB}

softkey.

(softkey level 4)

REVERS

ERROR

HOME

CALIB

AXIS

CALIB

SERVO

PARAM

SPNDL

PARAM

Once the

{AXIS CALIB}

softkey is pressed, the control displays the

following screens. The first screen only appears when no data has

been previously entered.

Figure 40.1

Initial Online Axis Calibration Screen

MEASURE(M)/DEVIATION(D)?

AXIS CALIBRATION

PAGE

1 of

1

X AXIS - 0.0000

[ MM ]

ABSOLUTE

DEVIATION

0 POINTS USE FOR AXIS X

1001 FREE

REPLCE

VALUE

INSERT

POINT

DELETE

POINT

UPDATE

& EXIT

NEXT

AXIS

Initially the control prompts you to select whether inputs should be

handled as measurements or deviations. If measurement is selected,

the user input is the actual reading. If deviation is selected, the user

input is the difference between the control reading and the

actual reading.