Rockwell Automation 8520-ARM2 9/Series CNC AMP Reference Manual Documentation Set User Manual
Page 685

Tuning AMP at the Machine
Chapter 40
40-7
Accessing Axis Calibration Parameters
Use this procedure to access the axis calibration parameters:
1.
Press the
{AXIS PARAM}
softkey.
(softkey level 3)
AXIS
PARAM
PATCH
AMP
UPDATE
BACKUP
UPLD/
DWNLD
BACKUP
AMP
2.
Press the
{AXIS CALIB}
softkey.
(softkey level 4)
REVERS
ERROR
HOME
CALIB
AXIS
CALIB
SERVO
PARAM
SPNDL
PARAM
Once the
{AXIS CALIB}
softkey is pressed, the control displays the
following screens. The first screen only appears when no data has
been previously entered.
Figure 40.1
Initial Online Axis Calibration Screen
MEASURE(M)/DEVIATION(D)?
AXIS CALIBRATION
PAGE
1 of
1
X AXIS - 0.0000
[ MM ]
ABSOLUTE
DEVIATION
0 POINTS USE FOR AXIS X
1001 FREE
REPLCE
VALUE
INSERT
POINT
DELETE
POINT
UPDATE
& EXIT
NEXT
AXIS
Initially the control prompts you to select whether inputs should be
handled as measurements or deviations. If measurement is selected,
the user input is the actual reading. If deviation is selected, the user
input is the difference between the control reading and the
actual reading.