Servo Parameters

Chapter 7

7-73

Important: On digital systems, if you use a standard motor, the correct

value for this parameter is entered automatically by the control when AMP

is downloaded or when the control is powered-up. When parameter

Standard Motor Table Values is set to “Yes”, then the control ignores the

value entered for this parameter and uses values as shown in Table 7.D and

Table 7.E.

Important: The velocity integral gain can be adjusted online using online

AMP capability of the control. However, if the parameter Standard

Motor Table Values is set to “Yes”, then the velocity integral gain is

automatically overwritten by the control upon power-up and when AMP is

downloaded.

The following tables are provided for reference only.

Table 7.D

Velocity Integral Gain Values for Standard 8500 Motors with Incremental Feedback

MOTOR:LOAD

INERTIA

8500 MOTOR TYPES

RATIO

8500

A1C

8500

A2C

8500

B1C

8500

B2C

8500

B3C

8500

A1D

8500

A2D

8500

A3D

8500

B1D

8500

B2D

1 : 0

112

96

128

128

128

112

101

98

128

128

1 : 1

224

192

256

256

256

224

202

196

256

256

1 : 2

336

288

400

400

400

336

303

294

400

400

1 : 3

640

640

640

640

640

640

640

640

640

640

MOTOR:LOAD

INERTIA

1326 MOTOR TYPES

RATIO

1326AB

B410G

B410J

1326AB

B420E

B520H

B730E

1326AB

B430E

B430G

1326AB

B515E

B515G

1326AB

B520E

B520F

1326AB

B530E

1326AB

B720E

1326AB

B740E

1 : 0

70

100

150

300

400

500

30

20

1 : 1

140

200

300

600

800

1000

60

40

1 : 2

210

300

450

900

1200

1500

90

60

1 : 3

280

400

600

1200

1600

2000

120

80