Patch AMP

Chapter 41

41-2

When AMP is modified using this utility, no cross-reference checking is

performed. This means that almost any value can be assigned to any

available parameter regardless of the consequences.

Patch AMP contains a limited number of the total available AMP

parameters and is not intended as a substitute for ODS. Its intended

purpose is to allow minor changes to be made to an already-existing AMP

that has previously been downloaded to the control from the ODS

workstation or some other peripheral device.

Assuming that the control is powered up and the highest access password

has been entered, use the following procedure to get to the

{PATCH AMP}

softkey:

1.

Press the

{SYSTEM SUPORT}

softkey.

(softkey level 1)

PRGRAM

MANAGE

OFFSET MACRO

PARAM

PRGRAM

CHECK

SYSTEM

SUPORT

FRONT

PANEL

ERROR

MESAGE

PASS-

WORD

SWITCH

LANG

2.

Press the

{AMP}

softkey.

(softkey level 2)

PRGRAM

PARAM

AMP

DEVICE

SETUP

MONI-

TOR

TIME

PARTS

3.

Press the

{PATCH AMP}

softkey. The control will prompt you for an

additional password to access the patch AMP utility.

(softkey level 3)

AXIS

PARAM

PATCH

AMP

UPDATE

BACKUP

UPLD/

DWNLD

BACKUP

AMP

Important: If the

{PATCH AMP}

softkey is not visible on this softkey level,

the currently active access level does not permit the use of this utility.

Return to softkey level 1, press the

{PASSWORD}

softkey, and enter the

highest level password (access level 0). This password is assigned using

the AMP parameters discussed in chapter 22 for the 1st - 6th character of

the password.

4.

The patch AMP password is the word LOCK. Type in LOCK using

the operator panel keyboard and press the

[TRANSMIT]

key. The

control will display the patch AMP utility screen.