Chapter 2

2-32

At the workstation:

1.

Return to the main menu line of ODS.

2.

Press

[F3]

to pull down the Applications menu.

3.

Select the Upload application.

4.

Press

[F4]

to pull down the utilities menu.

5.

Select the Get AMP params utility.

The workstation displays the Upload Origin screen.

6.

Select the Storage Device option.

7.

Type in a new file name for the file to be uploaded, then press

[ENTER]

.

Important: You must assign a new name to the AMP file that is

uploaded.

The workstation starts uploading the AMP file from the storage

device. The workstation continuously updates and displays the

percentage of the file that has been transferred.

When the upload process is complete, the workstation displays the

message:

UPLOAD COMPLETE

Press any key to return the workstation to the main menu line

of ODS.

When your current ODS project was created you were prompted to select a
communication type. If you selected and configured DH+ as the

communication mode you must also enable the 9/Series CNC to accept this

type of communication. The pass through feature sends AMP, PAL, or part

program configuration information out DH+ to a scanner device which in

turn passes that data on through remote I/O to the 9/Series. For this pass

through to work the 9/Series must have the pass through feature enabled.

There are three methods available to enable pass through:

AutoEnable -- If you system is equipped with the remote I/O hardware
and you do not enable the hardware for PAL use (using $RMON), DH+

pass through will automatically be enabled. AMP does not need to

enable block transfers for this method.

2.14

Enabling DH+ Pass Through