Servo Parameters

Chapter 7

7-82

Notes

This parameter must be set independently for each servo.

Function

Feed--to--Hard--Stop is only available on mill control types.

Use the Feed--to Hard--Stop feature when an axis is fed up to a fixed

mechanical stop that physically halts axis travel. This parameter

configures the torque that the servo must exert before the control identifies

a hard stop. Enter this torque value as a percentage of the servo’s

maximum rated torque. Refer to your operation and programming manual

for details on programming an axis against a hard stop using G24.

Axis

Number

Axis

Number

(1)

[1151]

(7)

[7151]

(2)

[2151]

(8)

[8151]

(3)

[3151]

(9)

[9151]

(4)

[4151]

(10)

[10151]

(5)

[5151]

(11)

[11151]

(6)

[6151]

(12)

[12151]

Range

1 to 300%

(a percentage of motor rated continuous duty current)

Notes

In order to perform feed to hard stop you must set the Servo Loop Type

parameter as either position/velocity or digital.

You must properly configure the parameter Maximum Rated Motor

Torque before attempting to use feed to hard stop.

This parameter must be set independently for each axis that uses the feed to

hard stop feature.

7.3.15

Hard Stop Detection Torque