Remote i/o parameters, 0 chapter overview 33.1 adapter baud rate, Chapter – Rockwell Automation 8520-ARM2 9/Series CNC AMP Reference Manual Documentation Set User Manual
Page 601: Function, Range

Chapter
33
33-1
Remote I/O Parameters
Use remote I/O communications to communicate data to/from a 1771
remote I/O scanner to/from your 9/Series control. Through remote I/O
communications, the control is seen as a remote rack to a 1771 remote I/O
scanner. The parameters in this section configure remote I/O
communications through the 9/Series control. Remote I/O communications
is available as an option on 9/Series controls.
When you select the Remote I/O Parameters group in AMP
this screen appears:
Proj:
AMPTEST
Appl:
AMP
Util:
Edit
F2-Project F3-Application F4-Utility
F5-Configuration
F1-File
F2-Axis
F3-Options
F4-Quick Edit!
F5-Process
Type : Lathe
AXIS: X <P1> - linear
P1:
File :
TEST
- Remote I/O Parameters -
Adapter Baud Rate
:
57.6K
Adapter Rack Number
:
3
Adapter Rack Size
:
FULL
Adapter Start Module Group
:
SQ0
Adapter Last Rack Status
:
Not last Rack
Adapter Block Transfer
:
Disabled
Function
This parameter specifies the baud rate of the remote I/O port. This value
must match your 1771 remote I/O network configuration.
Axis
Parameter Number
Mill/Lathe
Grinder
All
[140]
[145]
Range
Selection
Result
(a)
57.6K
(b)
115.2K
(c)
230.4 K
33.0
Chapter Overview
33.1
Adapter Baud Rate