Remote i/o parameters, 0 chapter overview 33.1 adapter baud rate, Chapter – Rockwell Automation 8520-ARM2 9/Series CNC AMP Reference Manual Documentation Set User Manual

Page 601: Function, Range

Advertising
background image

Chapter

33

33-1

Remote I/O Parameters

Use remote I/O communications to communicate data to/from a 1771
remote I/O scanner to/from your 9/Series control. Through remote I/O

communications, the control is seen as a remote rack to a 1771 remote I/O

scanner. The parameters in this section configure remote I/O

communications through the 9/Series control. Remote I/O communications

is available as an option on 9/Series controls.
When you select the Remote I/O Parameters group in AMP

this screen appears:

Proj:

AMPTEST

Appl:

AMP

Util:

Edit

F2-Project F3-Application F4-Utility

F5-Configuration

F1-File

F2-Axis

F3-Options

F4-Quick Edit!

F5-Process

Type : Lathe

AXIS: X <P1> - linear

P1:

File :

TEST

- Remote I/O Parameters -

Adapter Baud Rate

:

57.6K

Adapter Rack Number

:

3

Adapter Rack Size

:

FULL

Adapter Start Module Group

:

SQ0

Adapter Last Rack Status

:

Not last Rack

Adapter Block Transfer

:

Disabled

Function

This parameter specifies the baud rate of the remote I/O port. This value

must match your 1771 remote I/O network configuration.

Axis

Parameter Number

Mill/Lathe

Grinder

All

[140]

[145]

Range

Selection

Result

(a)

57.6K

(b)

115.2K

(c)

230.4 K

33.0

Chapter Overview

33.1

Adapter Baud Rate