Serial Transmission Function

MotionSuite™ MP940 Machine Controller Reference Manual

4-10

RS422/485 Interface Cable

1. Ensure that the drive system, control system, power system, and other

transmission systems are separate from each other.

2. The MP940 interface module RS422/485 interface is an MDR-14

female pin (Port 2).

3. The RS422/485 cable length is 300m maximum. Use the minimum

length necessary.

4. The MP940 module RS422/485 interface is a non-isolated system.

Errors may occur from noise in the connected terminal. If so, reduce
the noise by using a shield-type cable and modem.

5. In the case of RS422, insert a terminal resistor as needed. Make the ter-

minal on the receiving side.

6. In the case of RS-485, attach a terminal resistor to both ends of the

transmission line.