Status when alarm occurred – Yaskawa MP940 Reference Manual User Manual

Page 380

Advertising
background image

MotionSuite™ MP940 Machine Controller Reference Manual

Troubleshooting

10-27

A.C1

A.C1 is the alarm display for servo overrun. The alarm output appears
below.

Note: The indicates the output transistor is ON; the x indicates the output transistor is OFF

(alarm state).

Status when Alarm Occurred

Alarm Output

Alarm Code Output

ALM Output

ALO1

ALO2

ALO3

x

x

Cause

Remedy

A

Mistaken servo motor wiring.

Check wiring and connections at
servo motor.

B

Mistaken encoder wiring.

Check wiring and connections at
encoder.

C

Encoder defective.

Replace servo motor.

D

Circuit board (1PWB) defective.

Replace servo amplifier.

Alarm occurs at power ON

User parameter
Pn50A.1 = 7

D

Alarm occurs 1~3 seconds
after power ON

When Pn50A.1 is set
to other than 7

A, B, C, D

Alarm occurs at speed
reference input

A, B, C

Alarm occurs when servo ON
(/SV-ON) signal is ON

A, B, C, D