Status when alarm occurred – Yaskawa MP940 Reference Manual User Manual
Page 380

MotionSuite™ MP940 Machine Controller Reference Manual
Troubleshooting
10-27
A.C1
A.C1 is the alarm display for servo overrun. The alarm output appears
below.
Note: The indicates the output transistor is ON; the x indicates the output transistor is OFF
(alarm state).
Status when Alarm Occurred
Alarm Output
Alarm Code Output
ALM Output
ALO1
ALO2
ALO3
x
x
Cause
Remedy
A
Mistaken servo motor wiring.
Check wiring and connections at
servo motor.
B
Mistaken encoder wiring.
Check wiring and connections at
encoder.
C
Encoder defective.
Replace servo motor.
D
Circuit board (1PWB) defective.
Replace servo amplifier.
Alarm occurs at power ON
User parameter
Pn50A.1 = 7
D
Alarm occurs 1~3 seconds
after power ON
When Pn50A.1 is set
to other than 7
A, B, C, D
Alarm occurs at speed
reference input
A, B, C
Alarm occurs when servo ON
(/SV-ON) signal is ON
A, B, C, D