Start, Stop Sequence

3-3

DIP Switch Setting Method

The DIP switches on the CPU are used for start/stop sequence operation
control. The CPU module has six switches as shown in the figure below. The
function of each switch is shown in the following table.

Although “NO” is displayed on the arrow at the lower right side of the DIP
switches, flipping the switches to the right turns them ON, and left turns them
OFF.

Number

Name

Setting

Operation at Setting

Default
Setting

6

RUN

ON

User Program Run

ON

OFF

User Program Stop

5

INITIAL

ON

When SW4 is ON: Clear Memory

OFF

OFF

When SW4 is ON: Terminal mode

4

TEST

ON

Terminal Mode/Initialization Mode

OFF

OFF

Online

3

FLASH

ON

Program copy from FLASH to RAM

OFF

OFF

No program copy from FLASH to RAM

2

P.P
Default

ON

Default Port 1 only

OFF

OFF

Serial port setting

1

COPY

ON

M Register Copy when SW3 is ON
Turn the power ON when only SW1 is ON.
SGDH servo parameter in the controller is
transferred to SGDH .

to replace

SGDH.

OFF

OFF

No M Register Copy when SW3 is ON.
M Register has a battery backup.

6

5

4

3

2

1

NO

RUN

INIT

TEST

FLASH

P.P

COPY

ON

OFF