Inspection Items

MotionSuite™ MP940 Machine Controller Reference Manual

8-2

Periodic Inspection

The spot inspection items that must be executed once or twice every six
months to a year are detailed below. Execute these spot checks whenever the
installation has been moved or altered, if the wiring has been modified, etc.

Periodic Inspection Items

Do not change the internal fuse.

Customer replacement of the internal fuse may result in damage to the module or mis-

operation. Replacement of the internal fuse is to be performed by Yaskawa service

department personnel only.

Item

Inspection Items

Inspection

Content

Determination

Standard

Installation

1

Surrounding
Environment

Ambient
Temperature

Measure corro-
sive gas with
thermometer/
hydrometer

0 ~ 55ºC

When used in a panel,
the temperature within
the panel is the ambi-
ent temperature.

Ambient Humidity

30 ~ 95%RH

Atmosphere

No corrosive gas

2

Power Voltage Check

Voltage measure-
ment between
24VDC terminals

DC19.2 ~ 28.8V

Changing of supplied
power

3

Mounting
State

Looseness, rattling

Try running the
module.

These should be
securely mounted.

Tighten screws

Attachment of
grime, foreign
material²‚

Appearance

Nothing stuck to
unit

Removal, cleaning

4

Connection
State

Looseness in termi-
nal screws

Tighten with
screwdriver.

There must be no
looseness.

Tighten

Adjacent to contact
terminals

Appearance

Separation should
be normal.

Straighten

Connector
looseness

Appearance

There should be no
looseness.

Tighten the connector
fixing screws.

5

Battery

Check the “BAT”
LED on the front
panel of the
MP940.

The “BAT” LED
must be OFF.

Change the battery if
the “BAT” LED is ON.

CAUTION